Testing Frequencies
The Institute of Electrical Engineers has set out suggested initial frequencies of inspection and testing of electrical equipment as shown below.
|
Equipment use |
Type of equipment |
User checks |
Class I |
Class II |
||
|
Not recorded unless a fault is found |
Formal visual inspection (Note1)
Recorded |
Combined inspection and testing
Recorded |
Formal visual inspection (Note 1)
Recorded |
Combined inspection and testing
Recorded |
||
|
a |
b |
c |
d |
e |
f |
g |
|
Construction sites 110 V equipment |
S |
none |
1 month |
3 months |
1 month |
3 months |
|
IT |
none |
1 month |
3 months |
1 month |
3 months |
|
|
M (Note 2) |
weekly |
1 month |
3 months |
1 month |
3 months |
|
|
P (Note 2) |
weekly |
1 month |
3 months |
1 month |
3 months |
|
|
H (Note 2) |
weekly |
1 month |
3 months |
1 month |
3 months |
|
|
Industrial including Commercial Kitchens |
S |
weekly |
None |
12 months |
None |
12 months |
|
IT |
weekly |
None |
12 months |
None |
12 months |
|
|
M |
before use |
1 month |
12 months |
3 months |
12 months |
|
|
P |
before use |
1 month |
6 months |
3 months |
6 months |
|
|
H |
before use |
1 month |
6 months |
3 months |
6 months |
|
|
Equipment used by the public |
S |
Note 3,4 |
monthly |
12 months |
3 months |
12 months |
|
IT |
Note 3,4 |
monthly |
12 months |
3 months |
12 months |
|
|
M |
Note 3,4 |
weekly |
6 months |
1 month |
12 months |
|
|
P |
Note 3,4 |
weekly |
6 months |
1 month |
12 months |
|
|
H |
Note 3,4 |
weekly |
6 months |
1 month |
12 months |
|
|
Schools (Note 4) |
S |
Weekly |
None |
12 months |
12 months |
48 months |
|
IT |
Weekly |
None |
12 months |
12 months |
48 months |
|
|
M |
Weekly |
4 months |
12 months |
4 months |
48 months |
|
|
P |
Weekly |
4 months |
12 months |
4 months |
48 months |
|
|
H |
before use |
4 months |
12 months |
4 months |
48 months |
|
|
Hotels (Note 5) |
S |
None |
24 months |
48 months |
24 months |
None |
|
IT |
None |
24 months |
48 months |
24 months |
None |
|
|
M |
weekly |
12 months |
24 months |
24 months |
None |
|
|
P |
weekly |
12 months |
24 months |
24 months |
None |
|
|
H |
before use |
6 months |
12 months |
6 months |
None |
|
|
Offices and Shops
|
S |
None |
24 months |
48 months |
24 months |
None |
|
IT |
None |
24 months |
48 months |
24 months |
None |
|
|
M |
weekly |
12 months |
24 months |
24 months |
None |
|
|
P |
weekly |
12 months |
24 months |
24 months |
None |
|
|
H |
before use |
6 months |
12 months |
6 months |
None |
|
Notes
- The formal visual inspection may form part of the combined inspection and tests when they coincide, and is to be recorded.
- >110V earthed centre-tapped supply. 230V portable or hand-held equipment is required to be supplied via a 30mA RCD and inspections and tests carried out more frequently.
- For some equipment such as children's rides a daily check may be necessary.
- By supervisor/teacher/member of staff.
- Equipment provided in hotels rooms is equipment used by the public. Equipment in hotels (in table) is considered to be equipment in hotels used by the hotel staff.
- It is normally not necessary to test new items of equipment as the manufacturer has already tested them.
- The information on suggested initial frequencies given above is more detailed and specific than HSE guidance, but is not considered to be inconsistent with it.
IT Information Technology Equipment
M Movable Equipment
P Portable Equipment
H Hand-Held Equipment